| Help Desk |
| +91 44 2635 0628 |
|
|
|
|
|
|
|
|
|
| Technical Ventilation |
 |
| EN 14470-1 (safety storage cabinets for flammable liquids) |
 |
Cabinets shall be equipped with openings for inlet and exhaust air |
 |
The openings must close automatically when exposed to a temperature of 70 +/- 10 °C |
 |
The entire air inside a ventilated cabinet shall be exchanged at a rate of at least 10 times per hour, at a maximum pressure drop of 150 pa |
 |
Ventilation has to be effective directly above the bottom collecting sump |
|
| EN 14470-2 (safety storage cabinets for pressurised gas cylinders) |
 |
Cabinets shall be equipped with openings for inlet and exhaust air at least 120 times per hour for toxic gases; at a maximum pressure drop of 150 pa |
 |
Air circulation system within the cabinet shall ensure adequate purging from minor leakage |
|
| Advantages |
 |
Plug-in recirculating air filter system for safety storage cabinets (tall cabinets) type VBFA, VBFT, VBF and drum cabinets. |
 |
Safe air extraction of safety cabinets in work areas. |
 |
No expensive extraction piping necessary, easy and safe installation of the recirculating air filter system in two steps |
 |
Eliminates explosion risk area around the cabinet, high flexibility in choosing the installation location |
 |
Active personal protection through safe capture of harmful vapours with retention in the filter system |
 |
Ideal for use directly at the workplace - very low noise only approx. 39 dB |
|
 |
 |
|
|
 |
|
|
|
|